簡單有效地了解電弧故障檢測裝置 (AFDD)

電弧故障會構成嚴重的火災風險。探索電弧故障檢測背後的技術、相關安全標準,以及 SENTRON 電弧故障偵測裝置 (AFDD) 如何透過偵測危險電弧並立即中斷電流來解決電氣火災的根本原因。

Identifying and understanding the causes of fires

Many electrical fires start with arc faults

Arc faults pose a significant fire risk in electrical installations. They occur when electrical current jumps through the air – for example due to damaged cables or loose connections – generating high temperatures that can ignite nearby flammable materials. A distinction is made between:

  • Parallel arc faults: Contact between adjacent conductors such as phase and neutral caused by damaged or pinched cables
  • Series arc faults: Interruption in a single conductor caused by damaged insulation, crushed wires, or loose connections; often without overcurrent conditions
Typical causes of an arc fault, like damaged cables, kinked plugs, loosened contacts or environmental factors in general

使用 AFDD 偵測和中斷電弧故障

SENTRON protection devices deliver reliable electrical safety with coordinated MCB, RCD and AFDD protection

Modern safety technology ensures continuous protection

In electrical installations, short circuits, residual currents and arc faults create multiple risks. For continuous cable protection, personal safety and preventive fire detection, you need several protective components that work together:

  • Miniature circuit breakers (MCBs) offer protection against overload and short circuits
  • Residual current devices (RCDs) continuously monitor the current flowing in live and neutral wires. If they detect even a small difference, they instantly cut the power
  • AFDDs detect arc faults to help protect against resulting fires

AFDDs from the SENTRON portfolio provide reliable detection of series and parallel arc faults. They immediately interrupt the current flow – even in situations where conventional protective devices fail.

節省空間安裝 AFDD

在現代電氣裝置中,由於對控制、通信和安全技術的需求日益增加,主配電板、分配板和開關設備組件中的可用空間通常受到限制。但是,由於西門子 AFDD 的緊湊設計,因為空間不足,您不必犧牲防火防護。

西門子開發了一種特殊的 AFDD 變體,也非常適合在現有安裝中的電弧故障檢測裝置:SENTRON 5SV6 AVDD。它可以簡單地替換現有的微型斷路器,因為它已經集成了一個 MCB。此外,您還可以保留現有的引腳總線系統。

Space savings when retrofitting with the SENTRON AFDD 5SV6 pigtail

AFDD 標準和責任

DIN VDE 0100-420:2019 -10 定義了建築物電氣裝置的消防要求,包括配電系統。它建議在以下位置在最終電路中使用 AFDD:

  • 具有易燃建築材料的房間和位置(耐火等級低於 F30)
  • 帶睡房的客房(不論建築材料為何)
  • 對不可替代資產帶來風險的房間和位置
  • 根據模型建築守則(MBO § 2.19)具有特定火災風險的房間或位置

如果不安裝 AFDD 在這些位置,則該標準需要記錄的風險和安全評估,這可能很複雜且耗時。使用 SENTRON 產品組合中的 AFDD 是一個更簡單、更安全的解決方案。

Buildings with a particularly high risk of electrical fire

探索SENTRON產品組合

瞭解西門子產品如何協助您保護您的電氣系統。

SENTRON arc fault detection device

SENTRON 電弧故障偵測裝置 (AFDD)

使用 SENTRON 系列的電弧故障偵測裝置偵測所有類型的電弧故障。

SENTRON miniature circuit breaker

SENTRON 微型斷路器 (MCB)

安裝簡便,適用於多種應用場景。SENTRON 系列微型斷路器可幫助保護您的電氣系統免受過載和短路損害。

A Siemens powerpoint slide with a visual representation of a power system and a diagram of a power supply system.

SENTRON 剩餘電流保護裝置 (RCD)

SENTRON 系列的剩餘電流保護裝置是一套緊湊型解決方案,用於剩餘電流和線路保護,在發生電弧故障時立即安全地切斷電流。

Explore related AFDD resources